5. INSTALLATION
Read and follow the Safety Information set out in chapter 2 of
this document. Failure to adhere to any of the indications set
out in chapter 2 may cause a serious or very serious accident for those
who are in direct contact with the unit or who are in the vicinity, as
well as faults in the unit and/or in the loads connected to it.
In addition to the unit's user manual, other documents are supplied
on the documentation pen drive. Consult them and strictly follow
the indicated procedure.
The cross-sections of the cables used for the installation will be in
line with the currents indicated on the name plate, in compliance
with local Low Voltage Electrotechnical Regulations.
This chapter details the relevant requirements for locating and
wiring the
SLC CUBE4
its own location and installation particularities, the purpose of
this chapter is not to provide precise step-by-step instructions,
rather it should be used as a guide for the general procedures
and practices to be observed by
nised and defined in the EK266*08 safety instructions).
Unless indicated otherwise, all actions, indications, premises,
notes, etc. are applicable to the SLC CUBE4 units, whether or not
they form part of a parallel system.
5.1. RECEPTION.
All cabinets are supplied on wooden pallets that are mechanically at-
tached to them, with cardboard or wooden packaging according to the
model. Although the risk of tipping is minimal, they must be handled
with care, especially the taller cabinets and when there is a slope.
It is dangerous to handle the unit on the pallet in a careless
manner, as it could tip and cause serious or very serious
injuries to the operators, resulting from impact due to it possibly
tipping over and/or operators becoming trapped. Pay attention to
section 1.2.1. of the safety instructions -EK266*08- in all matters
relating to the handling, moving and positioning of the unit.
Use the most suitable means for moving the UPS when it is still
packed, with a pallet truck or forklift.
Any handling of the unit must be done paying attention to the
weights indicated in "Annex III. Technical specifications" according
to the model.
5.1.1. Reception, unpacking and contents
Reception. Check that:
The information on the label attached to the packaging
ˆ
corresponds to the information specified in the order. Once
the UPS is unpacked, check the above information with the
information on the unit's name plate.
If there are any discrepancies, deal with the non-con-
formity as soon as possible, citing the unit's manufacturing
number and the references on the delivery note.
It has not suffered any mishap during transport (packaging
ˆ
and impact indicator in perfect condition).
96
7.5-20 kVA UPS series. As each site has
qualified
staff (figure recog-
Otherwise, follow the protocol indicated on the label at-
tached to the impact indicator, located on the packaging.
Unpacking
To check the contents, the packaging must be removed.
ˆ
Complete the unpacking according to the proce-
dure in section 5.1.3.
Contents
UPS:
The unit itself.
ˆ
The user manual in electronic format [Pen Drive].
ˆ
1 RJ45 cable for connection with the Nimbus communica-
ˆ
tion card.
In the case of a parallel system, a set of parallel cables.
ˆ
Battery cabinet:
Battery connection bundle.
ˆ
Three battery fuses to be installed in the fuse holder dis-
ˆ
connect switch.
Once the reception process is complete, the UPS should be re-
packed until it is started up in order to protect it against mechanical
shock, dust, dirt, etc.
5.1.2. Storage
The unit must be stored in a dry, well-ventilated area, protected
from rain, dust, splashes of water or chemical agents. It is recom-
mended to keep each unit in its original packaging, as it has been
specifically designed to ensure maximum protection during trans-
port and storage.
For units that contain Pb-Ca batteries, the charging periods
indicated in Tab. 2 of document EK266*08 must be ob-
served, as well as the storage temperature to which they are ex-
posed, otherwise the warranty may be invalidated.
Data label for the model.
MUY IMPORTANTE PARA LA VIDA DE LAS BATERÍAS DE Pb-Ca:
su degradación deben ser recargadas en los intervalos indicados. Respetar
el procedimiento referido en el manual de usuario del equipo.
VERY IMPORTANT FOR THE LIFETIME OF Pb-Ca BATTERIES:
their degradation, they must be recharged according to the stated interval
times. Respect the procedure referred in the equipment user's manual.
Fecha carga /
Charging date :
**-**-****
Factory charging date noted.
Space to note the new charging date.
Fig. 26. Label on the packaging of the battery unit.
After this period, connect the unit to the mains together with
the battery unit, if applicable, start it according to the instruc-
tions described in this manual and charge for 12 hours.
Para evitar
ºC
Meses /
Months
In order to avoid
0 - 20
12
21 - 30
9
31 - 40
5
41 - 50
2,5
Fecha recarga /
Recharging date: