Télécharger Imprimer la page

Salicru SLC CUBE 4 7.5 kVA Mode D'emploi page 118

Publicité

Les langues disponibles

Les langues disponibles

118
Disabled*: the bypass is active.
ˆ
NeutralLineCheck: loss of neutral detection function.
Disabled: it deactivates the check function for the neutral
ˆ
line. The UPS will not detect if the neutral line has been dis-
connected.
Auto: the UPS will automatically detect if the neutral line
ˆ
has been disconnected or not. If a loss of neutral is detected,
the corresponding alarm will be generated. If the UPS is on,
it will switch to battery mode. When the neutral line is re-
stored and detected, the alarm will be muted automatically
and the UPS will return to normal mode automatically.
Verif.*: in contrast to the Auto setting, the alarm will
ˆ
NOT be muted automatically and the UPS will NOT return
to normal mode automatically until it is acknowledged
manually by pressing the Verif. function in order to vali-
date it.
ISO compensation:
It serves to compensate the voltage drop in the event that an
isolating transformer is connected to the UPS output.
Bypass UPS Off: it lets you select the static bypass status
when the UPS is stopped. The bypass will be activated provided
the "Prohibited bypass" function is disabled. "
Enabled*: bypass enabled. When selected, the stopped
ˆ
unit supplies voltage to the output via the bypass.
Disabled: bypass disabled. When selected, there is no
ˆ
output via bypass when turning the UPS off manually
(Standby mode).
Bypass VOL range: bypass voltage range setting.
Bypass VOL Range Low: the setting range is from 176
ˆ
V to 209 V.
Bypass VOL Range High : the setting range is from 231
ˆ
V to 264 V. Default setting: 196-264 V
Bypass FRE Range: bypass frequency range setting.
The acceptable frequency range is from 46 Hz to 54 Hz when
the system frequency is 50 Hz, and from 56 Hz to 64 Hz when
it is 60 Hz.
Default setting: 46-54 (50 Hz) / 56-64 (60 Hz).
ECO mode: a function that allows the ECO mode to be ena-
bled/disabled*. The default configuration is "Disabled". (see ECO
mode description in section 4.5.5).
ECO VOL Range: it adjusts the ECO mode voltage range.
ECO VOL Range Low: the setting range is from (nominal
ˆ
output voltage – 11 V) to (nominal output voltage - 24 V).
Default setting: "Nominal output voltage – 23 V".
ECO VOL Range High: the setting range is from (nominal
ˆ
output voltage + 11 V) to (nominal output voltage + 24 V).
Default setting: "Nominal output voltage + 23 V".
ECO FRE Range: it establishes the ECO frequency range. The
frequency range is from 46 Hz to 54 Hz when the frequency is 50
Hz, and from 56 Hz to 64 Hz when it is 60 Hz.
Default setting: 46-54 (50 Hz) / 56-64 (60 Hz)
*Default settings.
SALICRU

Publicité

loading

Ce manuel est également adapté pour:

Slc cube 4 10 kvaSlc cube 4 15 kvaSlc cube 4 20 kva