tribution will ensure that a fault in any of the machines connected
to the unit that causes a short circuit only affects the line that is
faulty. The other connected loads will have guaranteed continuity
due to the protection only being tripped on the line affected by the
short circuit.
For parallel systems, the connections that go from each unit to the
board must be repeated.
Finally, once the input and output connections have been
made, replace the protective cover of the terminals as shown
Fig. 38 a Fig. 41.
Fig. 38. Relocation of the protection cover of the tower version
connection terminals.
Fig. 39. Relocation of the protection cover of the rack version
connection terminals.
Fig. 40. UPS with the protection cover for the connection terminals
located in the tower version.
USER MANUAL
Fig. 41. UPS with the protection cover for the connection terminals
located in the rack version.
5.2.4. Connection of the unit's battery terminals to
those of the battery module.
As this unit has protection against class I electric
shocks, it is essential to install a protective earth
conductor (connect earth (
the earth terminal before supplying voltage to the input
terminals.
The original factory battery circuit type for external battery
modules is open.
– +
External battery cabinets are supplied with the fuses in a
bag. Insert them into the fuse holder disconnect switch
during start-up.
Do not handle the battery connectors and/or the
disconnect switch when the unit is running.
disconnect under load.
The battery cabinet is connected to the UPS using the cable
bundle supplied with each battery cabinet, connecting one
end to the UPS terminals and the other to the battery module
terminals, observing the polarity indicated on the labelling of
each element and in this manual. Observe the connections
according to cable colour: a UPS positive colour to a battery
cabinet positive; another UPS negative colour to a battery
negative; another UPS neutral colour to the battery middle tap
(N). Use the green-yellow cable to interconnect the earth con-
nections, see . Fig. 8, Fig. 9 and Fig. 10 show the battery con-
nectors and their respective earths in more detail.
Fig. 42. Connection between the UPS and one or several battery
cabinets..
SLC CUBE4 7,5 kVA a 20 kVA - UNINTERRUPTIBLE POWER SOIRCE (UPS)-
)). Connect this conductor to
Do not
103