"Language": you can select the display language of the
control panel, from the following options:
"English"
–
"Spanish"
–
"Portuguese"
–
"French"
–
"Date & Time": correctly configure the time (HH:MM:SS)
with the drop-down numeric menu corresponding to each
field.
Once set, return to the main screen by pressing this icon:
6.
HOME
CONTINUE THE START-UP ACCORDING TO THE INDI-
CATIONS DESCRIBED IN SECTION 6.1.3.
6.1.3. Generic start-up procedure (normal mode)
If you find the UPS completely shut down (see 6.2), but it had
been operating previously in the installation where it is located,
to restart it, proceed as indicated in this section.
If the UPS is simply in bypass mode (see 6.1.5), i.e. already sup-
plying power to the loads but via the static bypass, you can follow
the instructions in this section from point 6.
Supply general power to the control panel (external to
1.
the UPS).
Set the switch corresponding to the UPS input on the
2.
panel to
"On". If there is a separate bypass line, also set this
switch on the control panel to "On".
Connect the external batteries if the unit has them, in
3.
the case of B1 models (long
Set the input switch of the UPS to "On" (Q1) (only for
4.
tower format
devices). The screen boots, the fans start to
run and the main screen appears. The unit starts up in standby
mode, the "<41> Bypass Loss" warning appears on the screen
and the acoustic alarm sounds every second.
10 kVA
Standby Mode
231. 8 V
233. 5 V
232. 8 V
50.0 Hz
231. 8 V
233. 5 V
232. 8 V
50.0 Hz
<41> Bypass Loss
HOME
CONTROL
MEASURE
Set the corresponding bypass switch to "On" (Q4) (only
5.
for tower format devices).
pass input is connected internally to the rectifier.
By activating the bypass switch, the warning and the acoustic
alarm disappear and the unit switches to bypass mode, sup-
plying power to the loads via the bypass:
USER MANUAL
autonomy).
2020.11.04
11:56:35
0. 0 V
0. 0 V
0. 0 V
0.0 Hz
0%
218. 9 V
218. 8 V
9 AH
8%
SETTING
INFO
DATALOG
In standard units, the static by-
10 kVA
Bypass Mode
231. 8 V
233. 5 V
232. 8 V
50.0 Hz
231. 8 V
233. 5 V
232. 8 V
50.0 Hz
CONTROL
HOME
MEASURE
Press the
"Control"
6.
described in 7.2.
If the UPS stopped due to a power loss
7.
AC input and batteries, or end of autonomy),
operating in normal mode just before this, the UPS will
restart automatically at this point in online mode.
If the UPS does not start automatically ("Bypass Mode"),
8.
press the UPS ON/OFF icon.
The "Turn on UPS" pop-up box appears with the options
9.
"YES" and "NO". Press "YES".
10 kVA
Line Mode
UPS ON/OFF
BATT TEST
Turn On UPS?
MUTE ALL
EXIT PARALLEL
YES
HOME
CONTROL
MEASURE
Once validated, the main screen appears again with the on-
10.
screen message "Turning on",
10 kVA
Bypass Mode
231. 8 V
233. 5 V
232. 8 V
50.0 Hz
231. 8 V
233. 5 V
232. 8 V
50.0 Hz
HOME
CONTROL
MEASURE
and after a few seconds the unit will switch to online mode.
SLC CUBE4 7,5 kVA a 20 kVA - UNINTERRUPTIBLE POWER SOIRCE (UPS)-
2020.11.04
11:56:35
231. 8 V
233. 5 V
232. 8 V
50.0 Hz
1%
218. 9 V
218. 8 V
9 AH
9.5%
SETTING
INFO
DATALOG
icon. You are on the screen
(disconnection of
having been
2020.11.04
11:56:35
NO
SETTING
INFO
DATALOG
2020.11.04
11:56:35
Turning on...
231. 8 V
233. 5 V
232. 8 V
50.0 Hz
1%
218. 9 V
218. 8 V
9 AH
98%
SETTING
INFO
DATALOG