7.8.2. UPS warning table
Any warning implies that there is an anomaly in the UPS, which
indicates that a situation has occurred that could put the reliability
of the UPS at risk, but these situations do not immediately lead to
the interruption of the power supply.
WARNING
CODE
01
<01>BATT open
02
<02>IP N loss
04
<04> Line phase error
05
<05> Bypass phase error
07
<07> BATT over charge
08
<08> BATT low
09
<09> Overload warning
0A
<0A>Fan lock warning
0B
<0B> EPO active
0D
<0D> Over temperature
0E
<0E> Charge Fail
21
<21> Line connect dif
22
<22> Bypass connect dif
24
<24> Par INV vol dif
33
<33> Lock BYP OL 3 times
34
<34> AC input CURR unb
36
<36> INV CURR unb
3A
<3A> maintain is open
3C
<3C> Utility ext unb
3D
<3D> Bypass unstable
3E
<3E> BATT VOL High
3F
<3F>BATT VOL Unbalance
38
<38> BATT replace
41
<41> Bypass Loss
42
<42> ISO Over temp
45
<45> External output switch open
46
<46> Battery switch open
47
<47> Bypass switch open
48
<48> Input breaker open
Tab. 13. Warning messages by screen, classification and descrip-
tion.
USER MANUAL
MESSAGE ON-SCREEN
DESCRIPTION
Battery Open.
Input Neutral loss.
Line phase error.
Bypass phase error.
Battery Over Charge.
Battery low.
Over load warning.
Fan lock warning.
EPO active.
Over temperature.
Charger Fail.
The input(line) voltage of UPS is different in parallel system.
The input(bypass) voltage of UPS is different in parallel system.
Unbalanced load in parallel system. Parallel load different.
Locked in bypass after overload 3 times in 30 min.
AC Input current unbalance.
Unbalanced inverter current.
Cover of the maintain switch is open.
Utility extremely unbalanced.
Bypass unstable.
Battery Voltage High.
Battery Voltage Unbalance.
Battery replace warning.
Bypass Loss.
ISO over temperature.
When the external output switch is opened.
When external battery switch is disconnected.
When external bypass switch is disconnected.
When external line switch is disconnected.