Electrical installation
Mains connection

Connection plan for controllers type E82xVxxxK4C (400/500 V mains)

Connection plan for controllers type E82xVxxxK4C (400/500 V mains)
(
Stop!
Only connect the controller to the permitted mains voltage (^ Technical data). A
ƒ
higher mains voltage destroys the controller!
Some controllers may only be actuated with a mains choke or mains filter. This
ƒ
requirement can differ with regard to operation at rated power and operation at an
increased rated power.
The leakage current to earth (PE) is > 3.5 mA. In accordance with EN 61800−5−1 a
ƒ
fixed installation is required. The PE conductor has to be designed double.
3 PE AC 400 V
45 Hz -0 %...65 Hz +0 % 320 V -0 %...550 V +0 %
L1
L2
L3
N
PE
X1.1 PE L1
L2
L3
E82EVXXXK4C
X1.1/+UG, X1.1/−UG
Supply for DC−bus operation
118
0,7...0,8 Nm
6.2...7.1 lb-in
6 mm / 0.24 in
+UG -UG
l
X1.1
8200vec067
EDK82EV113 DE/EN/FR 11.0