Resetting fault messages

Eliminating the cause for TRIP error message
After eliminating the cause for a TRIP error message the error message must be reset with the "TRIP
reset" order. Only then the drive will start again.
)
Note!
A TRIP error message can have several causes. The TRIP reset can only be carried out
after all causes for the TRIP have been eliminated.
Manual or automatic TRIP reset
You can select whether errors occurred are to be reset manually or automatically. Mains
disconnection always carries out a TRIP reset independent of the settings under C0170.
)
Note!
If the controller carries out more than eight automatic TRIP resets within ten minutes,
the controller will set TRIP rST (Counter exceeded).
TRIP reset also resets the auto TRIP counter.
Codes for parameter setting
Code
No.
Name
C0043
TRIP reset
*
v
C0170
Configuration
v
of TRIP reset
C0171 Delay for auto
TRIP reset
EDK82EV113 DE/EN/FR 11.0
Troubleshooting and fault elimination
Possible settings
Lenze Selection
0
No current fault
1
Fault active
TRIP reset by mains switching, s,
0
0
LOW edge at X3/28, via function
module or communication module
1
Like 0 and additionally auto TRIP reset
2
TRIP reset by mains switching, via
function module or communication
module
3
TRIP reset by mains switching
0.00
0.00
Resetting fault messages
{0.01 s}
60.00
l
IMPORTANT
Reset active fault with C0043 = 0
l
TRIP reset via function module
or communication module
with C0043, C0410/12 or
C0135 bit 11
l
Auto TRIP reset automatically
resets all faults after the time
in C0171 has elapsed
8