Electrical installation
Mains connection
{
Danger!
Dangerous electrical voltage
The discharge current to earth (PE) is > 3.5 mA AC or 10 mA DC.
Possible consequences:
Death or severe injuries when touching the device in the event of an
ƒ
error.
Protective measures:
Implement the measures required in EN 61800−5−1. Especially:
ƒ
Fixed installation
–
PE connection must comply with standards (PE conductor diameter
–
³ 10 mm
X1
1a
8200mot009
0
R
= brake resistor (accessories)
B
³ 450 W (E82MV551/E82MV751)
R
B
³ 200 W (E82MV152/E82MV222)
R
B
EDK82MV222 DE/EN/FR 11.0
2
(Cu) or PE conductor must be connected twice)
0.5...0.6 Nm
4.4...5.3 lb-in
5.5 mm
PE
Fig. 5−0
l
Electrical installation
X1
L3 L2
L1
BR2 BR1 BR0 K14 K12 K11
BR2 BR1 BR0
A
R B
Vers.
152
3.4 Nm
30 lb-in
3/PE AC 320...550V 45...65Hz
L1
L2
L3
PE
F1
K1
X1
Mains connection
0.5...0.6 Nm
4.4...5.3 lb-in
2
2.5 mm
AWG 12
6 mm
Vers.
K14 K12 K11
151
X1
K12
K11
K14
-
+
L3 L2 L1
5
103
104
101