Electrical installation

Relay output connection

Relay output connection
Function
X1.2/K11
Relay output
normally−closed contact
X1.2/K12
Relay mid−position
contact
X1.2/K14
Relay output
normally−open contact
PES
HF shield termination by PE connection through shield clamp
)
Note!
Switching of control signals:
ƒ
Use shielded cables
HF shield termination by PE connection
The minimum load for switching the signals through correctly is 12 V and 5 mA.
Both values have to be exceeded at the same time.
Switching of mains potentials:
ƒ
Unshielded cables are sufficient
For the protection of the relay contacts a corresponding suppressor circuit is
ƒ
absolutely required for an inductive or a capacitive load!
The service life of the relay depends on the type of load (ohmic, inductive or
ƒ
capacitive) and the value of the switching capacity.
The message that is output can be changed in code C0008 or C0415/1.
ƒ
124
Relay position
Message
(activated)
(Lenze setting)
opened
closed
l
Technical data
TRIP
AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.16 A
TRIP
EDK82EV113 DE/EN/FR 11.0
8200vec013