Connection plan for controllers type E82xVxxxK2C (230/240 V mains)

Mains connection

Connection plan for controllers type E82xVxxxK2C (230/240 V mains)
(
Stop!
Only connect the controller to the permitted mains voltage (^ Technical data). A
ƒ
higher mains voltage destroys the controller!
Some controllers may only be actuated with a mains choke or mains filter. This
ƒ
requirement can differ with regard to operation at rated power and operation at an
increased rated power.
The leakage current to earth (PE) is > 3.5 mA. In accordance with EN 61800−5−1 a
ƒ
fixed installation is required. The PE conductor has to be designed double.
3 PE AC 230/240 V
45Hz -0%...65Hz +0% 100 V -0%...264 V +0%
L1
L2
L3
N
PE
X1.1 PE L1
L2
E82EVXXXK C 2
X1.1/+UG, X1.1/−UG
Supply for DC−bus operation
EDK82EV113 DE/EN/FR 11.0
L3
+UG -UG
Electrical installation
0,7...0,8 Nm
6.2...7.1 lb-in
6 mm / 0.24 in
l
Mains connection