Fuses and cable cross−sections according to EN 60204−1
Supply conditions
Range
Description
Fuses
l
Utilisation category: only gG/gL or gRL
Cables
Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).
RCCB
l
Controllers can cause a DC current in the PE conductor. If a residual current device (RCD) or a fault
current monitoring unit (RCM) is used for protection in the case of direct or indirect contact, only
one RCD/RCM of the following type can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for connection to a
1−phase system
Alternatively another protective measure can be used, like for instance isolation from the
environment by means of double or reinforced insulation, or isolation from the supply system by
using a transformer.
l
Earth−leakage circuit breakers must only be installed between mains supply and controller.
Observe all national and regional regulations!
Operation with increased rated power
,
System Manual
EDK82EV113 DE/EN/FR 11.0
Fuses and cable cross−sections according to EN 60204−1
l
Electrical installation
Mains connection
5
119