Electrical installation

Controller mains connection for a mains voltage of 400 V

Final works
5.3
Controller mains connection for a mains voltage of 400 V
(
Stop!
The user is responsible for sufficient strain relief!
Both, the master and the slave must be supplied!
ƒ
0
L1
L2
L3
BR1
PE
M8
L1, L2,
25-30 Nm
L3
221-264 lb-in
M6
PE
15-20 Nm
133-176 lb-in
Fig. 5−7
Fuses and cable cross−sections for the mains supply
EVF9381−EV
EVF9381−EVVxxx
EVF9382−EV
EVF9382−EVVxxx
EVF9383−EV
EVF9383−EVVxxx
5.4

Supply and fan connection at the controller for a mains voltage of 400 V/500V

(
Stop!
The user is responsible for sufficient strain relief!
86
BR2
U
V
W
PE
40 mm
Mains connection example
BR1, BR2
Brake resistor can only be operated with the variants V060 and V110
For connection see System Manual of 9300 vector
0
Master terminals
1
Slave terminals
Master
315
315
400
1)
Multiple conductor; both conductors must have the same cross−section
2)
Lenze recommends to use fuses of the gRL utilisation category
Observe the national and regional legislation
l
L1
L2
L3
PE
M8
L1, L2,
25-30 Nm
L3
221-264 lb-in
M6
PE
15-20 Nm
133-176 lb-in
Slave
Master
Slave
150
150
315
1)
2 × 50
2 × 50
150
150
315
1)
2 × 50
2 × 50
240
240
400
1)
2 × 95
2 × 95
1
BR1
BR2
U
V
W
PE
40 mm
9300VEC013
Master
Slave
95
95
1)
95
95
1)
150
150
1)
EDKVF9383 DE/EN/FR 4.0