7
Commissioning
Important codes for quick commissioning
Code
No.
Name
C0014
Operating mode
v
C0015
V/f rated
frequency
uSEr
C0016
V
boost
min
uSEr
C0034*
Range of
v
setpoint
selection
uSEr
Standard I/O
(X3/8)
152
Possible settings
Lenze
Selection
2
2
V/f characteristic control V ~ f
(linear characteristic with constant V
boost)
3
V/f characteristic control V ~ f
(square−law characteristic with constant
V
boost)
min
4
Vector control
5
Sensorless torque control with speed
limitation
l
Torque setpoint via C0412/6
l
Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)
50.00 7.50
à
0.00
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1
Current 4 ... 20 mA
2
Bipolar voltage −10 V ... +10 V
3
Current 4 ... 20 mA open−circuit monitored
min
2
{0.02 Hz}
960.00
40.00 à device−dependent
{0.01 %}
l
IMPORTANT
l
Commissioning is possible
without identifying motor
parameters
l
Advantage of identification with
C0148:
– Improved smooth running at
low speeds
– V/f rated frequency (C0015)
and slip (C0021) are calculated
and saved. They do not have to
be entered
In the case of the first selection enter
the motor data and identify them
with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be set =
0 (automatic DC injection brake is
deactivated)
l
C0015 is calculated and saved
during the motor parameter
identification with C0148.
l
The setting applies to all
permitted mains voltages
Setting applies to all permitted mains
voltages
Observe switch position of the
function module!
Reversal of rotation direction only
possible with a digital signal.
l
Minimum output frequency
(C0010) not effective
l
Individually adjust offset and gain
TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.
EDK82EV113 DE/EN/FR 11.0