Mains Connection 400 V; Fuses And Cable Cross-Sections - Lenze 8200 vector Instructions De Montage

Masquer les pouces Voir aussi pour 8200 vector:
Table des Matières

Publicité

Show/Hide Bookmarks
Show/Hide Bookmarks
45 Hz -0 %...65 Hz +0 % 320 V -0 %...550 V +0 %
L1
L2
L3
N
PE
Abb. 1-10
X1.1 PE L1
X1.1/+ UG, X1.1/-UG DC supply (DC-bus operation - see Operating Instructions)

Fuses and cable cross-sections

Type
Type
E82EV302K4B
E82EV402K4B 3/PE AC
E82EV552K4B
E82EV752K4B
E82EV113K4B
1)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: voltage 500 ... 600 V, tripping characteristic "H" or "K5"
2)
All-current sensitive residual current circuit breaker for the use with E82EVxxxK4B00x
3)
All-current sensitive residual current circuit breaker for the use with E82EVxxxK4B20x
4)
Flexible cable can only be connected using pin end connectors.
Observe national and regional regulations (e. g. VDE 0113, EN 60204)
Please observe the following when using e.l.c.bs:
E.l.c.bs must only be installed between mains supply and controller.
l
E.l.c.bs can trip incorrectly because of
l
– capacitive leakage currents of the cable shields during operation (especially with long,
shielded motor cables),
– simultaneous connection of several controllers to the mains supply,
– use of additional RFI filters.
L
3 PE AC 400 V
L3
L2
+UG -UG
E82EVXXXK4B
mains
mains
Installation to EN 60204-1
Fuse
M16 A
M16 A
3/PE AC
M25 A
320 ... 550 V;
320 ... 550 V;
45 ... 65 Hz
45 ... 65 Hz
M32 A
M32 A
Electrical installation

Mains connection 400 V

0,7...0,8 Nm
6.2...7.1 lb-in
6 mm / 0.24 in
Miniature
L1, L2, L3, PE
circuit
2
[mm
breaker
B16 A
2.5
B16 A
2.5
4)
B32 A
6
4)
B32 A
6
4)
B32 A
6
EDK82EV3 DE/EN/FR 2.0
Installation to UL
Fuse
L1, L2, L3, PE
]
[AWG]
15 A
14
15 A
14
20 A
10
25 A
10
25 A
10
3
X1.1
8200vec067
1)
FI
FI
≥ 300 mA
≥ 300 mA
2)
2)
≥ 30 mA
≥ 30 mA
3)
3)
13

Publicité

Table des Matières
loading