Switch−on sequence
15.
Enter the motor data
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depending on the controller
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depending on the controller
E
Motor cosj (C0091)
Lenze setting: Depending on the controller
16.
Start the motor parameter identification (C0148)
A
Ensure that the controller is inhibited
B
Set C0148 = 1
C
Enable the controller
If segment c becomes active again after approx. 30 s,
D
inhibit controller again.
17.
If necessary, select more parameters
When all settings are complete:
18.
Select setpoint
19.
Enable the controller
20.
The drive is now running.
EDK82EV113 DE/EN/FR 11.0
Parameter setting with E82ZBC keypad
Comment
See motor nameplate
Enter the value for the motor circuit
configuration (star/delta) selected!
Enter the value for the motor circuit
configuration (star/delta) selected!
Only when the motor is cold!
Terminal X3/28 = LOW
Pressv
l
Terminal X3/28 = HIGH
l
The identification starts:
– Segment c is off
– The motor consumes current and
– The motor does not rotate!
l
Terminal X3/28 = LOW
l
Identification is completed.
l
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)
l
Measured and stored:
– Motor stator resistance (C0084) = Total
Activate e.g. JOG frequencies (C0037, C0038,
C0039) or motor temperature monitoring
(C0119)
E.g. via potentiometer at terminals 7, 8, 9
Terminal X3/28 = HIGH
If the drive does not start, additionally press
u
l
Commissioning
Vector control
makes a high−pitched" tone.
resistance of motor cable and motor