Active Driver M/T 2.2 = Setting The Set Point P1 Function Of Input; O1: Setting Output 1 Function (Active Alarm)(Excluding A.d. M/M 1.1 And A.d. M/T 1.0); O2: Setting Output 2 Function (Pump Operating)(Excluding A.d. M/M 1.1 And A.d. M/T 1.0); Displays - DAB ACTIVE DRIVER M/M 1.1 Instructions Pour L'installation Et La Maintenance

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 24
8.6.13
ACTIVE DRIVER M/T 2.2 (excluding A.D. M/M 1.1 e A.D. M/T 1.0)
Setting the set point P1 function of input 2
When the parameter i2 is set at a value other than zero, with the input 2 it is possible to select one of
the two settable set points. The first is SP. The second is P1. The regulating range is from 1 to 9 bar.
8.6.14
O1: Setting output 1 function ( "active alarm" ) (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
O2: Setting output 2 function ( "pump operating ) (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
Assigning the parameters that associate functions with the digital outputs OUT1; OUT2
Assigning the
parameters
Each function is disabled.
o1
Each function is disabled.
o2
9.

DISPLAYS

9.1
DISPLAYS OF THE MAIN VALUES
Access key MODE
From normal operating status, pressing the MODE key displays the following values:
Fr: Display of the current rotation frequency (in Hz).

UP: Display of pressure (in bar).

C1: Display of the phase current of the electropump (in A).

(excluding A.D. M/M 1.1 and A.D. M/T 1.0)

UE: Display of the version of the software with which the appliance is equipped.

9.2
MONITOR DISPLAYS
Access keys SET and – for 2 seconds
From normal operating status, pressing the key SET and – enters the MONITOR function where the
following values are displayed:
(NB: to scroll through the values press the MODE key)
UF: Display of the flow
Display of the instantaneous flow.
Parameter to be used only as a reference in programming.

ZF: Display of zero flow

Display of the reading of the flow sensor on which zero was acquired (with electropump switched off).
During normal operation the ACTIVE DRIVER will use this parameter to switch off the electropump.
FM: Display of the maximum rotation frequency (in Hz)
tE: Display of the temperature of the power stages (in °C)
bt : Display of the temperature of the electronic card (in °C)
GS: Display of running status
SP = pump operating to maintain pressure "SP".
P1 = pump operating to maintain pressure "P1" (input 2 active).
AG = pump operating for "anti-frost".
FF: Display of fault history (+ and – to scroll through the alarms)
There is a queue of 16 positions for containing the last 16 faults which have occurred during system
operation. By pressing the – key you can go back in history and stop at the oldest fault present, whereas
by pressing the + key you can go forward in history and stop at the most recent fault present.
The decimal point identifies the last fault to have occurred in chronological order.
The history contains at the most 16 positions. Each new fault is inserted in the most recent position
(decimal point). For each fault after the sixteenth, the oldest one in the queue is erased. The history of the
faults is never erased but only updated as new faults occur. Manual reset and switching off of the
appliance do not erase the history of faults.
0
Each function is disabled.
Contact always open
Contact always closed
Each function is disabled.
Contact always open
Contact always closed
ENGLISH
Value
1
In case of blocking errors
the contact closes (default)
When the electropump is
operating the contact closes
49
2
In case of blocking errors
the contact opens
When the electropump is
operating the contact
(default)
(ref.Table no. 14 page 53)
(ref. Table no. 14 page 53)
3
opens

Publicité

Table des Matières
loading

Table des Matières