INDICATIONS ON THE DISPLAY

Identifying s.
Indications on the display in normal operation
Go
Electropump operating
Sb
Electropump waiting
User displays and settings
(keys MODE and SET 2 seconds )
SP
Setting the set-point pressure ( in bar ). Default: 3 bar
Installer displays and settings
(keys MODE and SET and – 5 seconds )
rC
Setting the rated current of the electropump ( in A )
rt
Setting the direction of rotation
Setting the rated rotation frequency of the electropump.
Fn
( in Hz )
od
Setting the operating mode
rP
Setting the pressure drop for restarting ( in bar )
Setting the interconnection address
Ad
(necessary on sets of several electropumps with exchange)
Eb
Enabling the booster
Technical assistance displays and settings
(keys MODE and SET and + 5 seconds )
tb
Setting the reaction time of the water lack blockage ( in s. )
GP
Setting the gain of the proportional coefficient of the PI
GI
Setting the gain of the integral coefficient of the PI
Setting the maximum rotation frequency of the electropump
FS
( in Hz )
Setting the minimum rotation frequency of the electropump.
FL
( in Hz )
Ft
Setting the low flow rate threshold
CM
Exchange method on sets of 2 electropumps
AE
Setting the enabling of the anti-block/anti-frost function
SF
Setting the starting frequency
St
Setting the starting time
i 1
Setting the function of input 1 (float)
i 2
Setting the function of input 2 (set point selection)
i 3
Setting the function of input 3 (enable )
Setting the auxiliary setpoint pressure (in bar)
P1
- in function of input 2 -
o1
Setting the function of output 1 (default value: 2; function: ON alarm )
o2
Setting the function of output 2 (default value: 2; function: ON operating )
Displays of the main values
(MODE key)
Fr
Display of the current rotation frequency (in Hz)
UP
Display of pressure (in bar)
C1
Display of the phase current of the electropump (in A)
Display of the version of the software with which the appliance is
UE
equipped
DISPLAY (keys SET and – for 2 seconds )
UF
Display of the flow
ZF
Display of zero flow
FM
Display of the maximum rotation frequency (in Hz)
tE
Display of the temperature of the power stages (in °C)
bt
Display of the temperature of the electronic card (in °C)
GS
Display of running status
FF
Display of the log of errors and blockages
Access to manual mode
(keys SET and + and – 5 seconds )
Setting the test frequency in manual mode (in Hz)
FP
≤ the set value FS
UP
Pressure display (in bar)
C1
Display of electropump phase current (in A)
rt
Setting the direction of rotation
UF
Display of flow
ZF
Display of zero flow
System reset
(keys MODE and SET and + and – )
General reset ( ZF appears when leaving reset and restarting )
ZF
ENGLISH
Description
53
Factory parameters
A.D.
A.D.
A.D.
M/M 1.1
M/T 1.0
M/T 2.2
3.0 bar
3.0 bar
3.0 bar
00
00
50
50
50
01
01
01
0.5 bar
0.5 bar
0.5 bar
"- -"
"- -"
02
02
10 s
10 s
10 s
1.0
1.0
1.0
1.0
1.0
1.0
50
50
50
0
0
0
15
15
15
01
01
01
01
01
45
1.0
01
01
01
2.5 bar
02
02
40
40
40
A.D.
A.D.
T/T 3.0
T/T 5.5
3.0 bar
3.0 bar
00
00
50
50
01
01
0.5 bar
0.5 bar
"- -"
"- -"
02
02
10 s
10 s
1.0
1.0
1.0
1.0
50
50
0
0
15
15
01
01
01
01
01
01
01
01
01
01
2.5 bar
2.5 bar
02
02
02
02
40
40