Functions; Regulating Modes; References Of Buttons, Signals And Components Of The Panel - DAB EEG0,75T3 S Serie Instructions De Mise En Service Et D'entretien

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 38
Terminals ref.
RS485
20 – 21 – 22
D.O.1
23 – 24 – 25
(ALARM)
D.O.2
26 – 27 – 28
A
B

9. FUNCTIONS

9.1

Regulating modes.

By means of the control board, the panels EEG-T3^S, EE2G-T3^S, EE3G-T3^S may be set to operate for two
different types of system:
- Water pressure booster set systems.
Regulation with constant relative pressure with internal PSET.
The pressure or head is set by means of the control board,
and remains constant, irrespective of the water request.
Regulation with constant relative pressure, with external PSET.
- Heating systems (circulators) with constant differential pressure.
Regulation with constant differential pressure with internal PSET.
This is set by means of the control board.
The head remains constant, irrespective of the water request.
Operation of only one circulator at a time, exchange of the starting order every 24 hours, automatic exchange to
the stopped circulator in the event of blockage of the operating circulator.
Operation of only one circulator at a time (default setting parameter 128).
Regulation with constant differential pressure with external PSET.

10. REFERENCES OF BUTTONS, SIGNALS AND COMPONENTS OF THE PANEL

The panels EEG-T3^S – EE2G-T3^S - EE3G-T3^S must be configured by means of the control board located on
the front of the panel, observing the signals on the display and setting the data with the keys described below.
REFERENCE
LL1
Ref. Photo 10.1
!
LL2
Ref. Photo 10.1
LL3
Ref. Photo 10.1
Connector of serial connection RS 485 on LOCAL PC;
present on board KL1.
Connector of serial connection RS 485 on REMOTE PC;
present on board KL1 .
Amber warning light indicating panel fed.
Red warning light indicating alarms.
Green warning light indicating electropump one running.
ENGLISH
FUNCTION
Connection terminals of the remote serial communication
RS485.
Terminals ref.: 20=Screen of the communication cable,
21=D +
22=D -
Connection terminals for remote alarm contact.
(parameter 301)
Terminals ref.: 23=NC, 24=COM. 25=NO. with panel not fed
or in alarm status.
(contacts without voltage. Characteristic 250V ac 5A)
Connection terminals of the remote contact for indicating the
functions set in the menu. (parameter 302)
Terminals ref.: 26=NC, 27=COM. 28=NO. with panel not fed
or in alarm status. (contacts without voltage. Characteristic
250V ac 5A)
FUNCTION
78
H
Q