english
7. Setting by means of control panel
At high system temperatures,
the pump may be so hot that only
the buttons should be touched
to avoid burns.
The pump control panel, fig. 19 or 20, incorporates the
following:
• Buttons,
and
, for setpoint setting.
• Light fields, yellow, for indication of setpoint.
• Indicator lights, green (operation) and red (fault).
Light fields
Indicator lights
Fig. 19:
Control panel for single-phase pumps
Light fields
Indicator
lights
Fig. 20:
Control panel for three-phase pumps,
7.1 Setpoint setting
The desired setpoint is set by pressing the button
or
.
The light fields on the control panel will indicate the set-
point set.
See examples in sections 7.1.1 and 7.1.2.
7.1.1 Pump in regulated operation
(pressure control)
Example:
Figure 21 shows that the light fields 5 and 6 are
activated, indicating a desired setpoint of 3 bar.
The setting range is equal to the sensor measuring
range (see sensor nameplate).
[bar]
6
3
0
Fig. 21:
Setpoint set to 3 bar, pressure-control mode
Buttons
Buttons
7.1.2 Pump in unregulated operation
Example:
In unregulated-operation mode, the pump performance
is set within the range from min. to max. curve, fig. 22.
H
Q
Fig. 22:
Pump performance setting, unregulated-operation mode
7.2 Setting to MAX-characteristic operation
Press
continuously to change to the MAX-characteristic
of the pump (top light field flashes). When the top light
field is on,
must be pressed for 3 seconds before the
light field starts flashing.
To return to unregulated or regulated operation, press
continuously until the desired setpoint is indicated.
H
Q
Fig. 23:
Max. curve duty
7.3 Setting to MIN-characteristic operation
Press
continuously to change to MIN-characteristic of
the pump (bottom light field flashes). When the bottom
light field is on,
must be pressed for 3 seconds before
the light field starts flashing.
To return to unregulated or regulated operation, press
continuously until the desired setpoint is indicated.
H
Q
Fig. 24:
Min. curve duty
7.4 Start/stop of pump
Stop the pump by continuously pressing
the light fields are activated and the green indicator light
flashes.
Start the pump by continuously pressing
desired setpoint is indicated.
until none of
until the
47