Setting
Switching mode, switching output 1 (Sm 1):
Switching output 1 is operating in
switching point / hysteresis mode.
Switching output 1 is operating in
window mode.
Switching direction, switching output 1 (S 1)
Normally open mode.
Normally closed mode.
Switch-on delay, switching output 1 (T on 1)
Time in seconds which must elapse once the
particular switching point has been reached or
exceeded before switching will occur.
Switch-off delay, switching output 1 (T off 1)
Time in seconds which must elapse once the
temperature has fallen below the particular switch-
back point before switching will occur.
Switching output 2, as described above.
Primary display (Primary)
Value which is to be continually displayed:
or
(for function, see section 5 Digital Display)
Status 17.08.2016
Actual temperature
Temperature, peak value
Temperature, lowest value
Display switched off
Switching point 1 or 2
HYDAC ELECTRONIC GMBH
Display
Setting
range
SP/ Win
ON/ OFF
0.00–99.99s
0.00–99.99s
ACT/
Top/
Min/
OFF/
S.P.1/
S.P.2/
Page 10
Initial
(default)
setting
SP
ON
0
0
ACT