8.2. SUMMARY OF THE BASIC SETTINGS

Setting
Switching direction relay 1 (Relay 1)
E
"ON":
The relevant relay is activated
when the switching point is
reached, and deactivated
when the temperature falls below
the switch-back point.
"OFF": The relevant relay is activated in
the quiescent state (0 °C / 32 °F),
and deactivated when the
switching point is reached.
Switch-on delay relay 1
(T
1)
on
Time in seconds which must elapse,
once the particular switching point has
been reached or exceeded, before
switching will occur.
Switch-off delay relay 1
(T
1)
off
Time in seconds which must elapse,
once the temperature has fallen below the
particular switch-back point, before
switching will occur.
Relays 2..4 as above
Switch-back mode (Switch Mode)
"R.S.P": The ETS 1700 operates with
adjustable switch-back points.
"HYST": The ETS 1700 operates with
adjustable hystereses.
(see also point 6.1 "Relay outputs")
28
Display
Setting
range
ON/OFF
0..900s
0..900s
R.S.P./
HYST.
Pre-
setting
ON
0.1
0.1
HYST.