SUMMARY OF THE BASIC SETTINGS

Settings
Switching output 1 assignment (S.S.1) *
Switching output 1 is supposed to
switch to the pre-set fluid level
Switching output 1 is supposed to
switch to the pre-set temperature
Switching mode, switching output 1 (S.m.1)
Switching output 1 is operating in
switching point hysteresis mode
Switching output 1 is operating in
window mode
Switching direction, switching output 1
(S.d.1)
Normally open
Normally closed
Switch-on delay, switching output 1 (T
Time in seconds which must elapse once the
particular switch point has been reached or
exceeded before switching will occur.
Increment: 1s
Switch-off delay, switching output 1 (T
Time, in seconds, which must elapse once
the value has dropped below the switch back
point before a switching operation will occur.
Increment: 1s
Settings for switching output 2, 3 or 4 are carried
out as described above
Primary display (Primary)
Value to be continually displayed:
Actual fluid level
Peak fluid level
Lowest fluid level
Current temperature
Peak temperature
Lowest temperature
to
Display off
(For function, see Section 6 "Digital display")
Version 2018/07/06
ON
OFF
Switch point 1 to 4
HYDAC ELECTRONIC GMBH
Display
1)
1)
Setting
Default
Range
settings
niv / TEMP
niv
SP / Win
SP
ON / OFF
ON
0 .. 9999s
1
0 .. 9999s
1
niv/
niv
n.Top/
n.Min/
Temp/
T.Top/
T.Min/
S.P.1/
S.P.2/
S.P.3/
S.P.4/
OFF
Part No. 669927
Page 15