6
7 Settings
By using the programming unit HPG 3000, it is possible to make the following settings in the
EDS 4000:
7.1
Switch point settings
E
7.2
Hysteresis settings (Switch-back point)
7.3
Switching direction (N/O or N/C-function)
7.4
Switch on delay
7.5
Switch off delay
Status: 16.06.2015
This sets the switch value at which the switching output will switch when the
value is exceeded (above or below) according to its pre-set switching
direction (see 7.3).
Abbreviations: "SP.1"
"SP.2" = Switching point 2
(only on units with two switching points)
This sets a hysteresis to the switching point. The switching output switches
back if the value falls below the switch-back point. The switch-back point is
determined by the pre-set hysteresis (switch-back point = switching point
minus hysteresis).
Abbreviations:
"HYS.1"
"HYS.2"
(only on units with two switching points))
The switching direction determines if the switching function is to be normally
open or normally closed. (on = N/O-function / oFF = N/C-function)
Abbreviations: "S.d.1"
"S.d.2"
(only on units with two switching points)
Time in milliseconds [ms] which must elapse, once the switching point has
been reached or exceeded, before switching will occur.
Abbreviations: "T.on1"
"T.on2"
(only on units with two switching points))
Time in milliseconds [ms] which must elapse, once the pressure has fallen
below the particular switch-back point, before switching will occur.
Abbreviations: "T.oF1"
"T.oF2"
(only on units with two switching points)
HYDAC ELECTRONIC GMBH
= Switching point 1
= Hysteresis SP1
= Hysteresis SP2
= Switching direction SP1
= Switching direction SP2
= Switch on delay [ms] SP1
= Switch on delay [ms] SP2
= Switch off delay [ms] SP1
= Switch off delay [ms] SP2
EDS 4000 programmable
Part No.: 669737