6.
Basic settings
in order to adapt the unit to a particular application, the function of the
eds 3000 can be altered via several basic settings. these are combined
in a menu.
E
6.1. altering tHe basic settings
important note:
when the menu is activated no switching operations are carried out.
switch off supply voltage or disconnect the unit from the supply voltage.
press "mode" key
display
press "mode" key
and hold down.
(release
until required
switch on supply
"mode"
menu point appears.
voltage (hold key
key)
then release the key
down for 3s)
(see summary 6.2.)
to close the basic setting menu:
call up the menu point "EnD", set to "YES", the eds 3000 returns to the
normal display mode after 2 seconds.
note:
if after about 25 seconds no keys have been pressed, the menu
automatically closes down. any changes which may have been made will not
be saved.
38
change setting with
or
,
then choose next point in
the menu
6.2. summary of tHe basic settings
setting
Switching mode switching output 1 (Sm 1)
switching output 1 operates in
switching point / hysteresis function
switching output 1 operates in
window function
Switching direction switching output 1 (S 1)
n/o function
n/c function
Switch-on delay switching output 1
(t
1)
on
time in seconds which must elapse, once
the particular switching point has been
reached or exceeded, before switching will occur.
Switch-off delay switching output 1
(t
1)
off
time in seconds which must elapse, once
the pressure has fallen below the particular
switch-back point, before switching will occur.
Switching output 2 is set
as described above
Primary display (Primary)
display value which should remain
permanently in the display:
actual pressure
pressure peak value
switching point 1 or 2
or
display off
(for function, see point 4 " digital display")
Reset time (RTIM)
indicates how long
the last peak pressure is
shown on the display .
display
setting
pre-
range
setting
sp/ win
sp
on/off
on
0.00..99.99s 0
0.00..99.99s 0
act/
act
top/
s.p.1/
s.p.2/
off
0 .. 300s
0
E