Mettler Toledo IND570 Manuel D'installation page 95

Masquer les pouces Voir aussi pour IND570:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 330
2.4.6.6.
DeviceNet PLC Option
The DeviceNet PLC option board (Figure 2-110) is installed in position 3 (Figure 2-94) on the
main board. The DeviceNet option board is connected to the network by a DeviceNet-specific
twisted pair cable.
2.4.6.7.
EtherNet/IP – Modbus TCP PLC Option
The EtherNet/IP – Modbus TCP PLC option (Figure 2-111) is installed in position 3 (Figure 2-94)
on the main board. The EtherNet/IP-Modbus TCP PLC option connects to the network via a standard
Ethernet patch cable. The module's address is set in software, and the DIP switches are not used
and must all be set to OFF.
2-62
METTLER TOLEDO IND570 Terminal Installation Manual
Figure 2-110: DeviceNet PLC Option Board and Wiring
Notes for DeviceNet option wiring:
Connection with 2 twisted-pair shielded cables, Belden 3082A or 2083A or equivalent.
Refer to ODVA DeviceNet documentation (http://www.odva.org) for other considerations.
Wire sizes: 14 AWG max./22 AWG min.
Figure 2-111: EtherNet/IP-Modbus TCP Option Board
30205319
|
11
|
07/2019

Publicité

Table des Matières
loading

Table des Matières