Figure 2-106: Solid State Output Wiring, 8 Outputs
Notes for Solid State Discrete I/O Output wiring:
Solid State MOSFET control
Rating:
AC: 60 VAC max., 500mA into resistive load
DC: 60 VDC max., 500mA into resistive load
All inductive loads must be suppressed
Wire size: 24 AWG (0.2 mm
2
) min./18 AWG (0.8 mm
METTLER TOLEDO IND570 Terminal Installation Manual
2
) max.