TECHNICAL DATA

Operating voltage
Power consumption
Output current
Operating temperature
Noise resistance
Noise emission
Inputs:
Signal inputs
Accuracy
Connection
Outputs:
Cable outlet
Number of terminals
Type of contact
Controller:
Control algorithm
Sampling time TA
Amplification factor KP
Integral action time TN
K-Faktor 1 und 2
Verhältnis
Calibration
Housing:
Degree of protection
Material / Mounting
Dimensions / Weight
Order No.
Control unit type 8624-B for the compact pressure controller
Order No.
Settings of the compact pressure controller at delivery
Calibration
Selection
Calibration of set-value input
Set-value
KP
TN
1)
The operating unit Type 8624-B is not included in the standard delivery of the compact pressure
controller Type 8624.
Operating Manual No. 800 215
24 V DC
max. 1,5 W
max. 1,0 A
-10 to + 60 C
to EN50082-2
to EN50081-2
2 standard signal inputs 4 - 20 mA
±1% of full scale
in unit: 7-pole terminal + PE
Wire cross-section max. 0,5 mm²
PG 9 fitting
Cable φ 6 - 7 mm
can be turned in 90° steps
2 poles and earth
Surface contact, similar to a flat plug
(DIN 46 247/48)
PI controller
30 ms
0 ... 99,99
0,1 ... 199,99 s
0,0 ... 1999,9
0,01 ... 9,99
0 ... 199,99
IP 65
Polyamide / M 3x45mm cheesehead
screws
32 x 90 x 41,5 mm / approx. 50g
134 073 L
1)
134 053 Q
0 - 10
internal set-value (C.01)
0 - 10
1,00
1,00
0,50
27