General Data; Technical Data; Conditions Of Use - Burkert 8030 Manuel D'utilisation

Masquer les pouces Voir aussi pour 8030:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Hall
12-36 V DC
Hall Low
energized via the
Power
Bürkert transmitter
the flow sensor is
connected to
Ordering codes of fitting S030 can be found within the
related data sheet: refer to the data sheet to select the
fitting appropriate to the process.
English
12
type of fluid
conditions
Fluid group 2 § 1.3.b DN ≤ 200

General data

Pipe diameter
DN6 to DN65
The appropriate diameter is deter-
mined using the flow rate / DN / fluid
velocity graphs.
Pressure class
Depends on the material of the fitting
used and on the fluid temperature:
refer to the operating instructions of
the fitting used.
Fluid temperature
The fluid temperature may be restricted
by the fluid pressure: refer to the ope-
rating instructions of the fitting used.
• with fitting S030 in
• -15 to +100 °C
metal or PVDF
• with fitting S030
• 0 to +80 °C
in PP
• with fitting S030 in
• 0 to +50 °C
PVC
Type and data of the
refer to the operating instructions of
fluid
the fitting used.
English
14
2 transistors,
NPN and
423913
PNP
1 NPN
transistor
423914
6.

TechnicAl DATA

conditions of use

Ambient temperature
-15 °C to +60 °C
(operating)
Air humidity
< 80%, non condensated
Protection rating
IP65, female connector wired,
plugged and tightened
conformity to standards and
directives
The device conforms to the EC directives through the
following standards:
• EMC: EN 61000-6-2, EN 61000-6-3
• Pressure: The S030 fitting complies with article 3 of §3
from 97/23/CE directive.
Acc. to pressure directive 97/23/CE, the fitting can only
be used in the following cases (depending on the max.
pressure, the DN of the pipe and the fluid):
type of fluid
conditions
Fluid group 1 § 1.3.a only DN ≤ 25
Fluid group 2 § 1.3.a DN ≤ 32
or DN > 32 and PNxDN ≤ 1000
Fluid group 1 § 1.3.b PNxDN ≤ 2000
Flow rate measuring
0,3 to 10 m/s
range
≤ ±
Accuracy, with standard
(0.5 % of the full scale + 2.5 % of
K factor
the measured value)*
Linearity
≤ ± 0,5 % of the full scale (10 m/s)*
± 0,4 % of the measured value*
Repeatability
* Determined in the following reference conditions: medium =
water, water and ambient temperatures 20 °C, min. upstream and
downstream distances respected, appropriate pipe dimensions
English
13
13
English
15
15

Publicité

Table des Matières
loading