Internal Default Set-Value (C.01); External Default Set-Value (C.02); Lower Limit Value - Burkert 8624 Instructions De Service

Régulateur / compact de pression d'écoulement
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.3.6 Internal default set-value (C.01)

è Set the set-value within the limits of the calibration selected in Paragraph
7.3.3.
Setting the pre-comma value of the internal set-value
Setting the post-comma value of the internal set-value

7.3.7 External default set-value (C.02)

è For external default set-values, enter a scale limit.
The flow range corresponding to the standard signal (4-20 mA) must be set, i.e.,
the input of the flow at 4 mA (lower limit value) and at 20 mA (upper limit value)
takes place.
Example:
7.3.7.1

Lower limit value

è Limit the lowest control range using the lower limit value
NOTE:
With external set-values (standard signals) the error message
E.02 appears as soon as a signal less than 4 mA is read in.
38
Lower limit value
Upper limit value
Increase of the pre-comma value
Proceed to set the post-comma
value
Increase of the post-comma value
Continue from 7.3.8
0 bar
10 bar
4 mA
20 mA
Type 8624