The electrical connection of all the devices is made through
a male fixed connector.
12-36 V DC
2 transistors,
filtered and
NPN and
regulated
PNP
energized via the
1 NPN
Bürkert transmitter
transistor
the flow sensor is
connected to
without
1 sinus
output
English
12
Acc. to pressure directive 97/23/CE, the device can only
be used in the following cases (depending on the max.
pressure, the DN of the pipe and the fluid):
type of fluid
conditions
Only DN ≤ 25
Fluid group 1 § 1.3.a
DN ≤ 32
Fluid group 2 § 1.3.a
or DN > 32 and PNxDN ≤ 1000
DN ≤ 25
Fluid group 1 § 1.3.b
or DN > 25 and PNxDN ≤ 2000
DN ≤ 400
Fluid group 2 § 1.3.b

General data

Tab. 1:
Temperature-pressure dependency curves
P (bar)
11
10
9
PVDF
8
PVC + PP
7
6
5
4
PVC (PN10)
3
2
1
0
-10
+10
+30
English
14
Hall, short
419587
Hall, long
419589
Hall Low
Power,
419591
short
Hall Low
419593
Power, long
Coil, short
419583
Coil, long
419585
A
Metal
PVDF (PN10)
PP (PN10)
T (°C)
+50
+70
6.

TechnicAl DATA

operating conditions

Ambient temperature
-15 °C to +60 °C
Air humidity
< 80%, non condensated
Protection rating
IP65 acc. to EN 60529, female
connector wired, plugged and
tightened
conformity to standards and
directives
The device conforms to the EC directives through the fol-
lowing standards:
• EMC: EN 61000-6-2, EN 61000-6-3
• Vibration: EN 60068-2-6
• Shock: EN 60068-2-27
• Pressure: Article 3§3 of the Pressure Directive 97/23/CE.
Pipe diameter
DN20 (except for DN20 specified
p.27) to DN400. The appropriate
diameter is determined using the flow
rate / DN / fluid velocity graphs.
Pressure class
Depends on the material of the fitting
used and on the fluid temperature.
See Tab. 1
Fluid temperature
The fluid temperature may be restricted
by the fluid pressure: Refer to the
temperature-pressure dependency
curves for the device. See Tab. 1
• with fitting S020 in
• -15 to +80 °C
metal or PVDF
• with fitting S020
• 0 to +80 °C
in PP
• with fitting S020 in
• 0 to +50 °C
PVC
Flow rate measuring
Hall and Hall Low Power versions: 0,3
range
to 10 m/s
Sinus version: 0,5 to 10 m/s
≤ ±
Accuracy, with standard
(0.5 % of the full scale + 2.5 % of
K factor
the measured value)*
≤ ±0,5 % of the full scale*
Linearity
±0,4 % of the measured value*
Repeatability
* Determined in the following reference conditions: medium =
water, water and ambient temperatures 20 °C, min. upstream and
English
13
13