Automatic Transfer Switch
OPTIONS
ATyS 3e, 6e, 6s
Communication module
SAVE COMMAND (RESET)
This command must be completed to save modified
parameters. 0 must be set to address 0600.
>
Example: for slave n° 5
Slave
Function
05
>
NB:
ATyS won't answer. Save command is followed by a
complete reset (software version displayed on LCD).
TEST / CONTROL
>
Command
Slave
Function
05
06
>
Reading
Slave
Function
05
03
132
ATyS
Value
high-order
06
06
Add. Pf
high order
low order
$04
Add. Pf
high order
low order
$01
Value
low-order
00
Add. Pf
Value Pf
high order
1 bit /function
• bit 0=1: test
on load
• bit 1=1: test
off load
$80
• bit 2=1: Control
Pos 1
• bit 3=1: Control
Pos 0
• bit 4=1: Control
Pos 2
Add. Pf
Value Pf
high order
1 bit /function
if bit = 0:
no test
• bit 0=1: test
on load
• bit 1=1: test
$22
off load
• bit 2=1: Control
Pos 1
• bit 3=1: Control
Pos 0
• bit 4=1: Control
Pos 2
Communication module
Values
CRC 16
0000
88C6
Value Pf
CRC
low order
1 = start
CRC
0 = stop
Value Pf
CRC
low order
1 bit /function
if bit = 0:
no test
• bit 0=1:
started via I/O
CRC
• bit 1=1:
started via
interface
• bit 2=1: started
via Comm
SOCOMEC - Réf.: 531 848 F