Control circuits ATyS 6s
Denomination Terminals* Description
Power supply Power 101 Source
1
230 V~102
Power supply Power 201 Source
2
230 V~202
Sensing inputs N (103) Neutral
1
source
L3 (104) Phase 3
L2 (105) Phase 2
L1 (106) Phase 1
Sensing inputs L1 (203) Phase 1
2
source
L2 (204) Not connected
L3 (205) Phase 3
N (206) Not connected
Commands
207
Commands inputs Common terminal
208
Standby source transfer control input
209
Remote test on load input
210
Not connected
Genset
73
Genset start / stop relay - 2 stable positions
start signal**
74
Programmable state - factory setting = NO, close to start 5A AC1 / 250 V
Position
13
Common I - 0 - II
auxiliary
14
AC position I NO
contacts
24
AC position II NO
34
AC position 0 NO
Options
81
Common AC position I
Second
82
AC position I NC
position
84
AC position I NO
auxiliary
91
Common AC position II
contacts
92
AC position II NC
94
AC position II NO
Voltage sensing precision: 1 %
* Terminal numbers can be different in the case of voltage sensing and power supply kit connection (refer to kit specific
configurations).
** Refer to programming, setup, to change output relay state.
SOCOMEC - Réf.: 531 848 F
1
2
Automatic Transfer Switch ATyS
CONNECTIONS
Characteristics
220 to 240 Vac ±20 %
500 Vac (phase-phase)
maximum
288 Vac (phase-neutral)
maximum
500 Vac (phase-phase)
maximum
Do not connect
to any power supply
Dry contact
5A AC1 / 250 V
5A AC1 / 250 V
Recommended
section
1.5 mm
2
1.5 mm
2
1.5 mm
2
2
1.5 mm
4 mm
2
1.5 mm
2
1.5 mm
2
91