socomec ATyS 3e Notice D'utilisation page 115

Masquer les pouces Voir aussi pour ATyS 3e:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Programming
>
Menu Timer
1 2
LCD
Denomination
Main Failure
Timer
1 2
Delay on
transfer Timer
1 2
O Main failure
Timer
1 2
Main return
Timer
1 2
O main return
Timer
1 2
Cool down
Timer
1 2
>
Communication Menu
Menu only activated in case of optional
communication module connection
(refer to Options chapter).
LCD
Denomination
Address
1 2
Speed
1 2
Stop bit
1 2
Parity bit
1 2
SOCOMEC - Réf.: 531 848 F
Definition
Delays priority network failure detection
Standby network stability validation before transfer
Rest in O position when transferring
from main network to standby network
Main network stability validation before re-transfer
Rest in O position when re-transferring from standby
network to main network
Allows generator cooling down period after load's
retransfer from standby source (generator) to Main source
1 2
Definition
Address of the device
Communication speed
Automatic Transfer Switch ATyS
OPERATION
ATyS 6s & 6e
Setting
range
from 0 to 60 s
from 0 to 60 s
from 0 to 20 s
from 0 to 30 min
from 0 to 20 s
from 0 to 30 min 4 min
Setting
range
1 to 247
2400, 4800,
9600, 19 200,
38 400
1, 2
No, odd, even
6s 6e
Default
values
5 s
5 s
5 s
1 min
5 s
6s 6e
Default
values
5
9 600
1
No
115

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Atys 6sAtys 6e

Table des Matières