Programming
>
Volt Menu
1 2
Threshold detection starts from the loss of source
or source return sequence
%
Controlled value (voltages)
100
LCD
Denomination / Definition
Network 1 over voltage threshold
1 2
Network 1 over voltage threshold hysteresis
1 2
Network 1 under voltage threshold
1 2
Network 1 under voltage threshold hysteresis
1 2
Network 2 over voltage threshold
1 2
Network 2 over voltage threshold hysteresis
1 2
Network 2 under voltage threshold
1 2
Network 2 under voltage threshold hysteresis
1 2
Values definition: % of nominal values
Hysteresis values range is limited by thresholds values.
SOCOMEC - Réf.: 531 848 F
Automatic Transfer Switch ATyS
OPERATION
ATyS 6s & 6e
Over voltage threshold (oU)
Over voltage hysteresys
threshold (oUh)
Available source
t
Under voltage hysteresys
threshold (uUh)
Under voltage threshold (uU)
Setting
range
from 102 to
120 %
from 101 to
119 % (<oU)
from 80 to 98 % 85 %
from 81 to 99 %
(>uO)
from 102 to
120 %
from 101 to
119 % (<oU)
from 80 to 98 % 85 %
from 81 to 99 %
(>uU)
Default
values
115 %
110 %
95 %
115 %
110 %
95 %