Operation - socomec ATyS 3e Notice D'utilisation

Masquer les pouces Voir aussi pour ATyS 3e:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Automatic Transfer Switch

OPERATION

ATyS 6s & 6e
Operation
PRESENTATION
This mode allows in manual position (not padlocked) to
start a test off load. In the automatic position, it allows
the starting of a test, on or off load and to control elec-
tricaly the position of the changeover switch on ATyS 6e.
Enter operation mode:
• Step 1: press and hold
the "mode" push button for 5 s
• Step 2: enter the operation code (CE) using
navigation push buttons (code 4000)
• Step 3: press "validation"
push button
OPERATION MODE ARCHITECTURE
Led "test on load"
is blinking
1 2
Led "test off load"
is blinking
1 2
Led "control"
is blinking
1 2
* only on ATyS 6e.
118
ATyS
Enter: press 5 seconds
Yes, press
"validation"
Led "TEST ON LOAD"
is fixed
No, press
"mode"
Yes, press
"validation"
Led "TEST OFF LOAD"
is fixed
No, press
"mode"
Yes, press
"validation"
Led "CONTROL 1 O 2 "
is fixed
No,
press "mode"
Exit: press 5 seconds
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
Exit operation mode:
Press and hold for 5 s
"mode" push button
Navigate in operation mode:
• Press "mode" push button to access
different features
• Press "validation" push button to activate
required function
TEST ON LOAD
Loss of priority
source sequence
TEST OFF LOAD
Genset start
sequence
Changeover switch
Led "contrôle"
position control 1 O 2
fixe
(PS1, PS 0, PS2)
SOCOMEC - Réf.: 531 848 F

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Atys 6sAtys 6e

Table des Matières