OPERATION
ATyS 6s & 6e
Programming
>
Inputs/Outputs Menu
Menu activated in case of 2I / 2O optional module
connection (up to 2 modules).
Refer to accessories mounting for Input &
Output terminals identification.
Input state can be configured: NC or NO.
LCD
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
• Inputs:
Ft1, Ft2: External Fault 1or 2. The fault led is blinking as
soon as the input is active and Ft1or Ft2 is displayed
on LCD. Reset when the input is de-activated
PRI: Priority network selection. Network 1 has priority
when input is not activated. Network 2 has priority if
input is active.
This information is the only considered in case
of option configuration. Programming variable
Pri is then inhibited.
116
ATyS
1 2
Denomination / Definition
Input 1
State input 1
Input 2
State input 2
Input 3
State input 3
Input 4
State input 4
Output 1
Output 2
Output 3
Output 4
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
In case of option re-plug or de-plug action,
inspect Inputs / Outputs identification and
programming.
Output relays are NO type (construction) and
can not be configured as NC.
Setting range
Ft1, Ft2, Pri, Mtf, S2A, /
NO, NC
Ft1, Ft2, Pri, Mtf, S2A, /
NO, NC
Ft1, Ft2, Pri, Mtf, S2A, /
NO, NC
Ft1, Ft2, Pri, Mtf, S2A, /
NO, NC
S1A, S2A, LS, /
S1A, S2A, LS, /
S1A, S2A, LS, /
S1A, S2A, LS, /
Mtf: Remote manual re-transfer. Feature identical to
manual re transfert on keypad. Re-transfer from prio-
rity network to standby network is allowed from input
activation (1s front). The Mtf variable in the setup menu
must be selected (Yes) to allow input recognition.
Refer to priority source return sequence.
S2A: Information source 2 available (Genset) used instead
of voltage/frequency measurement from ATyS (inhibited
when S2A is selected).
Refer to loss of priority source sequence.
6s 6e
Default values
/
NO
/
NO
/
NO
/