Automatic Transfer Switch
OPERATION
ATyS 6s & 6e
Programming
PARAMETERS CHARACTERISTICS
>
Menu Setup
1 2
LCD
Denomination
Type of
network*
1 2
Network
nominal voltage
1 2
Network**
nominal
1 2
frequency
Source 1 - Switch I
or II configuration
1 2
Genset start
signal state
1 2
Network priority
selection
1 2
Manual
Retransfer
1 2
Type of control
logic selection**
1 2
Number of
permutation
1 2
counter Reset
Programming
code
1 2
modification
* refer to annexes
** on ATyS 6e only.
112
ATyS
Definition
Number of active conductors of controlled network
(refer to annexes)
Phase-Neutral voltage for 1BL & 41NBL
Phase-Phase voltage for others
Network nominal frequency
1
Source
(controlled and displayed) linked to switch I or II
(depending on cabling)
Normally opened or closed
Keypad selection (1 or 2)
Also possible via external contact
Using option
Activation of the feature
Impulse or contactor
1
Allows source
-> source
counter reset
Possible to change the programming code
2
automatic sequences
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
Setting
Default
range
values
1BL, 2BL,
4NBL
2NBL, 3NBL,
4NBL, 41 NBL,
42 NBL
from 110 V to
400 V
480 V
50 Hz or 60 Hz
50 Hz
I
I, II
NO or NC
NO
1 or 2
1
1
(
)
(
1
2
or
)
Yes or No
No
Imp, con
Imp
Yes or No
No
from 0001 to
1000
9999