Quietqube® Ice Machine Head Section - Manitowoc INDIGO NXT QUIETQUBE 816 Manuel D'installation, D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Section 2
ICVD1496
ICVD1895
ICVD1896
ICVD2095**
ICVD2096**
* Indicates preliminary data - Subject to change
**ICVD2095 Only - Verify the direction of the rotation is correct on the 3ph scroll compressor. The ice machine will have high suction pressure,
low discharge pressure and will be noticeably loud. Reverse two incoming power leads to reverse rotation.
QUIETQUBE
ICE MACHINE HEAD SECTION
®
Ice Machine
I0600C - I0686C
I0870C - I0876C
I0970C
IB0600C
IB0870C - IB0876C
IB1070C - IB1076C
I1070C - I1076C
I1176C
I1470C - I1476C
208-230/1/60
I1870C - I1876C
I2170C - I2176C
** All conductors must be solid copper wire
Part Number 000007924 5/14
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
208-230/1/60
208-230/3/60
Voltage
Maximum
Phase
Fuse/Circuit
Cycle
Breaker
115/1/60
15 amp
230/1/50
15 amp
115/1/60
15 amp
230/1/50
15 amp
115/1/60
15 amp
230/1/50
15 amp
115/1/60
15 amp
230/1/50
15 amp
115/1/60
15 amp
230/1/50
15 amp
115/1/60
15 amp
15 amp
230/1/50
15 amp
20 amp
11.7
15 amp
8.9
20 amp
11.7*
40 amp
25.0
25 amp
20.0
40 amp
25.0
40* amp
25.0*
25* amp
20.0*
30* amp
20.0*
40 amp
30.0
20 amp
20.0
50 amp
40.0
30 amp
30.0
Minimum
Total
Circuit
Circuit
Required by Manitowoc
Amps
Amps
1.1
N/A
1.5
1.1
N/A
1.5
1.1
N/A
1.5
1.1
N/A
1.5
1.1
N/A
1.5
1.1
0.8
N/A
1.5
#10 Solid Copper Conductor
#12 Solid Copper Conductor
#8 Solid Copper Conductor
#8 Solid Copper Conductor
#10 Solid Copper Conductor
#8 Solid Copper Conductor
#8 Solid Copper Conductor
#10 Solid Copper Conductor
#8 Solid Copper Conductor
#6 Solid Copper Conductor
#10 Solid Copper Conductor
#6 Solid Copper Conductor
#10 Solid Copper Conductor
Minimum Breaker
**Minimum Wire Size
#14 Solid Copper
Conductor
#14 Solid Copper
Conductor
#14 Solid Copper
Conductor
#14 Solid Copper
Conductor
#14 Solid Copper
Conductor
#14 Solid Copper
Conductor
Installation
Size Required by
Manitowoc
15 amp
15 amp
15 amp
15 amp
15 amp
15 amp
15 amp
15 amp
15 amp
15 amp
15 amp
15 amp
15 amp
15