Electrical Requirements; Icvd Condensing Units - Manitowoc INDIGO NXT QUIETQUBE 816 Manuel D'installation, D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation

Electrical Requirements

Local or state electrical code, length of wire run or materials used, can increase the minimum wire or breaker size
requirement. A qualified electrician must determine the wire and breaker size, although the minimum wire size must
meet or exceed the specifications in these charts. Refer to the condensing unit serial plate to verify electrical data.
Important
Due to continuous improvements, this information is
for reference only. Please refer to the condensing
unit serial number tag to verify electrical data. Serial
tag information overrides information listed on this
page.

ICVD CONDENSING UNITS

Condensing Unit
Voltage/Phase/Cycle
ICVD0695
ICVD0696
ICVD0895
ICVD0896
ICVD0996
ICVD1095
ICVD1096
ICVD1195
ICVD1195
Bristol
Compressor
ICVD1196
ICVD1495
14
Maximum Fuse/
Circuit Breaker
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
208-230/1/60
208-230/3/60
230/1/50
ICVD2095/ICVD2096 ONLY
Connect power supply wiring directly to L1 & L2 on
the contactor. Torque screws to the torque value
specification on the contactor label. Follow all local,
state and national electrical codes.
Minimum Circuit
Amps
15 amp
11.0
15 amp
7.5
15 amp
11.0
15 amp
11.6
15 amp
10.2
15 amp
10.2
20 amp
11.8
15 amp
9.1
20 amp
11.8
20 amp
11.8
15 amp
9.1
20* amp
11.8
20 amp
12.5
15 amp
9.5
20 amp
12.5
20 amp
15.0
15 amp
15.0
20 amp
15.0
20* amp
15.0*
15* amp
15.0*
20* amp
15.0*
25 amp
14.5
15 amp
9.3
35 amp
15.7*
25 amp
14.2
15 amp
9.5
35 amp
15.7*
35* amp
25.0*
25* amp
20.0*
35* amp
25.0*
20 amp
20.0
15 amp
15.0
20amp
20.0
Section 2
!
Warning
Minimum Wire Size Required
by Manitowoc
#12 Solid Copper Conductor
#12 Solid Copper Conductor
#12 Solid Copper Conductor
#12 Solid Copper Conductor
#12 Solid Copper Conductor
#12 Solid Copper Conductor
#10 Solid Copper Conductor
#12 Solid Copper Conductor
#10 Solid Copper Conductor
#10 Solid Copper Conductor
#12 Solid Copper Conductor
#10 Solid Copper Conductor
#10 Solid Copper Conductor
#12 Solid Copper Conductor
#10 Solid Copper Conductor
#10 Solid Copper Conductor
#12 Solid Copper Conductor
#10 Solid Copper Conductor
#10 Solid Copper Conductor
#12 Solid Copper Conductor
#10 Solid Copper Conductor
#8 Solid Copper Conductor
#10 Solid Copper Conductor
#8 Solid Copper Conductor
#8 Solid Copper Conductor
#10 Solid Copper Conductor
#8 Solid Copper Conductor
#8 Solid Copper Conductor
#10 Solid Copper Conductor
#8 Solid Copper Conductor
#10 Solid Copper Conductor
#12 Solid Copper Conductor
#8 Solid Copper Conductor
Part Number 000007924 5/14