supply hook-up point, so that voltage drops under
full load do not exceed 4% (10% during start-up)
compared with the rated voltage specified on the
data plate.
- The operator must:
compliance with the relevant safety standards;
nection - A, Fig. 2 - and fit a differential safety
circuit-breaker with 30 mA residual current;
as indicated on the general wiring diagram in this
manual;
the machine must not be connected to domestic
sockets.
An effective grounding connection is essential for correct operation of the machine.
Make sure the available pressure and the rendered capacity of the compressed air system
are compatible with those required for correct machine operation - see the "Technical Data"
section. For correct machine operation, the compressed air supply line must provide a
pressure range from no less than 8.5 bar to no more than 16 bar and guarantee an air flow
rate greater than the average consumption of the machine, which is equal to 187 Nl/min.
For correct equipment operation, the air produced must be suitably treated (not
above 5/4/4 according to ISO 8573-1)
Check that the Lubricator unit B fig. 2a contains air
lubricating oil; top up if necessary. Use SAE20 oil.
The customer must provide an air cut-off valve upstre-
am of the air treatment and regulator device supplied
with the machine.