Sauna/SANARIUM
7.
System settings
Call up the service menu
'
See page 21.
)* With SANARIUM controller 18033/18040 with function.
)* With Sauna controller 18029/18040 without function (changes to these values are
not applied).
7.17. Service menu 16 - T_OF, heater operating hours
Display:
Time in hours that the heater has been in operation.
Operating hours > 9999 can be read on the serial PC interface.
7.18. Service menu 17 - T_VD, evaporator operating hours)*
Display:
Time in hours that the evaporator has been in operation.
Operating hours > 9999 can be read on the serial PC interface.
7.19. Service menu 18 - TEMP, "Austria" setting
Input:
0
=
Inactive/100 °C
2
=
Inactive/110 °C
In SANARIUM mode, the evaporator can be switched on by entering 1 or 3 with a target temperature
of > 52 °C.
7.20. Service menu 19 - VENT, exhaust air
Input:
0
=
Fan
7.21. Service menu 20 - KEY, KEYGUARD
Input:
0
=
KEYGUARD function disabled
2
=
Remote activation with remote
power-on unit connected
7.22. Service menu 21 - GREE, Green Sauna
Input:
0
=
Green Sauna disabled
2
=
Green Sauna with fan run-on
50701290/12.14
1
=
Active/100 °C
3
=
Active/110 °C
1
=
Electric cover flap
1
=
KEYGUARD function enabled
3
=
CBC/remote power-on without
KEYGUARD
1
=
Green Sauna enabled
PAGE 25