Sauna/SANARIUM
7.
System settings
Call up the service menu
'
See page 21.
7.36. Service menu 35 - SM_P, Calibrating the heat-up phase
Calibrating the heat-up phase for switching on via remote start, preset time mode or the app.
.
Prerequisites:
Only carry out this process when the cabin and the sauna heater are cold. Otherwise, the
measured values will be distorted and the monitoring will not work correctly during operation.
1.
Select menu 35.
d
The calibration process is started until a Delta T of 5 Kelvin is reached.
d
If a Delta of 5 Kelvin is reached, the measured time (e.g. 240 seconds) remains the same
-> Display of temperature 5.0 (Kelvin) and 240 (seconds).
2.
Press OK to confirm the displayed values.
d
Menu 35 SM_P and the flashing value 5 are displayed.
3.
Press OK to confirm the displayed value.
d
The measured value (e.g. 240 seconds) is read out and displayed along with the value 50
(5.0 Kelvin).
4.
Press OK to confirm the displayed values.
d
The values are saved.
5.
Select the END menu and press OK to confirm.
d
The controller restarts. After restarting, the controller is ready to switch on via remote start, preset
time mode or the app.
.
Activate the determined heat-up phase measured values for the sauna heater type.
Set service menu 34 SM_I to the value 5, see page 28.
7.37. Service menu 36 - END, exit service menu
To exit the service menu, select the last service menu (END) using the +/- symbols and confirm by
pressing the OK symbol.
50701290/12.14
PAGE 29