Télécharger Imprimer la page

Kessel Aqualift F Guide D'installation Et De Maintenance page 61

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 89
5.6 Configuration of switch unit (up to model year 12/09)
Configuration of the control is carried out in the factory using switches S601 ... S604 between the terminal blocks of the level
inputs and thermal protection input. For safety reasons, these must be checked according to the following descriptions.
Pre-settings or reference settings are highlighted grey.
- Basic setting is carried out using switch S604 (4-way DIP switches with 2 positions ON / OFF each).
- Deviating settings are not allowed.
up to year 12/09
S604 / 1
S604 / 2
S604 / 3
S604 / 4
All manuals and user guides at all-guides.com
5. Electrical connections
ON
(wastewater lifting system)
Run-time controlled System
Submersible pump
without OFF level switch
Rotary field/phase monitoring
on
Anti-blocking function
on
61
OFF
Level-controlled system
(submersible pump system)
Submersible pump
with OFF level switch
Rotary field/phase failure monitoring
off
Anti-blocking function
off

Publicité

loading

Ce manuel est également adapté pour:

Aqualift f duo