11.1 Alarms on the display
When a fault occurs:
• The RESET LED comes on
• If enabled, local and remote audible alarms are activated
• A pop-up screen appears on the display, showing the alarm code and description:
11.1.1 Alarm list
The table describes the main alarms: for more information, refer to the Control Display
Operating Manual.
GEM, GEMJ – Fire-fighting Pump Set
Press RESET to reset the alarm: if the alarm cannot be reset it means that the fault that
caused it is still present.
Code
Description
A01
Low mains voltage
A02
High mains voltage
A03
Low mains frequency
A04
High mains frequency
A05
Asymmetric mains voltage
A06
No phase
A07
Incorrect phase sequence
A08
Failure to start
A09
Rotor blocked
A10
Dry run
A11
Current too low
A12
Current too high
A13
Unbalanced currents
A14
Unexpected current
A15
Wrong TA connection
A16
System error
A17
Low pump room temperature
A18
High pump room temperature
A22
Low priming tank level
A24
Pump running
A25
Pump not under pressure
A26
Pump under pressure
Cause
Mains voltage below the P05.01 limit
Mains voltage above the P05.02 limit
Mains frequency below the P05.03 limit
Mains frequency above the P05.04 limit
Mains voltage asymmetry above the P05.05 limit
Phase missing
Incorrect phase sequence
• Motor not started with a current 10% higher than the rated current,
within the times defined in menu M05, or
• Input programmed using the "Pump pressure switch" function not closed
Motor current higher than the 500% of the rated current for more than 5
seconds
The pump is running empty; measured power factor below the P05.13 limit
The motor current is below the P05.06 limit
Motor current above the P05.07 limit
Maximum current asymmetry limit set in P05.14 exceeded
Current 5% higher than the rated current detected
One or more current transformers are not connected correctly, negative active
power is measured; check the connections of terminals 57, 58, 59 and 60
Internal error, contact Xylem or the Authorised Distributor
The temperature of the pump room is below the P04.02 limit for a time
longer than set in P04.03
The pump room temperature is above the P04.04 limit for a time longer than
set in P04.05
Insufficient water level in the priming tank
Start the pump
"Pump pressure switch" function not active, with motor started, for 1 minute
"Pump pressure switch" function active, with motor started, for 1 minute
en – Original Instructions
111