Switching on the control panel
1. Set the selector switch to 0.
2. Turn the main switch to I-ON.
3. Check that the main display page shows:
4. Check that there are no alarms.
5. If the system includes automatic shutdown, enable parameter P02.16.
6. If necessary, enable the automatic test.
8.6.2 Manual start test and system filling
1. Set the selector switch to MAN.
2. Open the pump set discharge on-off valve half way.
3. Locate the arrow on the adapter, the coupling or the cover, to determine the correct
4. Start the motor by pressing MAN.
5. Check the rotation direction through the motor cover.
6. Fully open the valve to change the system pressure to the value set on the pressure
7. Stop the motor by pressing STOP.
8.6.3 Commissioning test
Preparation
1. Set the selector switch to MAN.
2. Close the following valves:
3. Check that the system is pressurised (no flashing PRESS message on the display).
4. From the main menu of the control display access the START-UP page with the advanced
Test
1. Set the selector switch to AUT.
2. Press ► (extended pressure) to test the switching on of the LEDs.
3. Check that the system is pressurised (no flashing PRESS message on the display).
4. Open the flow rate test control valve.
5. Press ◄ to start the motor.
6. Wait 5 minutes.
7. Close the control valve.
8. Stop the motor by pressing STOP.
9. Open the on-off valve at the fire-fighting system discharge.
102
• The mains voltage
• "0" operating mode.
DANGER:
Enabling the automatic test makes the operating cycle not compliant with the
UNI EN 12845:2015 standard. For more information, refer to the Control
Display Operating Manual.
direction of rotation of the motor.
switches: check the pressure with the pressure gauge.
• on-off valves at the discharge of the fire-fighting system
• Adjustment for flow rate test.
level PIN code:
1.
LED Test
2.
Start-up test
GEM, GEMJ – Fire-fighting Pump Set