en – Original Instructions
110
Problem
Causes
The motor runs but no
No water
water is delivered
Air in the suction pipe or inside the pump
The suction pipe is leaking water
Check valve jammed
Clogged suction pipe
Three-phase motor turning in the wrong direction
The pump is leaking
Worn mechanical seal
water
The weight of the piping system is putting
pressure on the pump
The pump produces
Cavitation
excessive noise or
The pump does not turn freely due to a
vibrations
mechanical fault
Water back flow when stopping the pump
The pump does not
Insufficient suction pipe diameter
prime
or with too many changes in direction
Trapped distribution pipe effect
Clogged piping system
Air in the suction pipe
Foot valve clogged
Foot valve locked in closed or partially closed
position
On-off valves partially closed
The pump does not
Water leaks in the system
stop when the STOP
Float switch with open contact
button is pressed
The performance of the
Clogged piping system
pump set is lower than
Foot valve clogged
required
Foot valve locked in closed or partially closed
position
On-off valves partially closed
The water requirements of the pump set are
greater than the flow rate provided by the supply
source
Air in the suction pipe
Undersized pump set
Three-phase motor turning in the wrong direction
The motor vibrates
Protection fuse blown
Loose fuse box
Faulty fuse box
Contactor contacts worn or faulty
The pump does not turn freely due to a
mechanical fault
Worn bearings
Solutions
1. Open the on-off valves
2. Fill the piping system and the pump with water
Check the piping system connections and bleed
the pump
Check the NPSH; correct the system as necessary
Clean the valve
Remove the clogging
Check the direction of rotation and change if
necessary
Replace the mechanical seal
Ensure independent piping system support
Increase the NPSH available in the system
Contact Xylem or the Authorised Distributor
Check the check valve
Check the installation
Remove the clogging
Complete a pressure test and check the tightness
of the connections, joints and piping system
Remove the clogging
Replace the foot valve
Fully open the valves
Check the installation
1. Check the water level inside the priming tank
2. Check the float switch
If the problem continues, replace the float switch
Remove the clogging
Remove the clogging
Replace the foot valve
Fully open the valves
Increase the flow rate
Complete a pressure test and check the tightness
of the connections, joints and piping system
Contact Xylem or the Authorised Distributor
Check the direction of rotation and change if
necessary
Replace the fuse
Tighten the fuse box
Replace the fuse box
Replace the contactor
Contact Xylem or the Authorised Distributor
Replace the bearings
GEM, GEMJ – Fire-fighting Pump Set