181 Guard code
To change the settings:
1. On the control unit, enter:
2. The LCD display shows: 181:GuardCodeOFF
UK
3. Via the keypad, select from the following items and
press:
0
1
4. Confirm your input. On the control unit, enter:
5. The control unit acknowledges your input with a
double "beep" tone and shows Installer Mode.
182 Last output for settling time
This time sets a delay in the alarm report for detectors in the
exit area. The sirens are switched off during this time and the
alarm centre ignores the alarms.
To change the settings:
1. On the control unit, enter:
2. The LCD display shows: 182:Settling 07
3. Via the keypad, select from the following items and
press:
07-12
4. Confirm your input. On the control unit, enter:
5. The control unit acknowledges your input with a
double "beep" tone and shows Installer Mode.
183 Change display
To change the settings:
1. On the control unit, enter:
2. The LCD display shows: 183: Terxon M
181
GuardCodeOFF
No guard code is used
GuardCodeON
Using the guard code, the user can
deactivate the alarm centre after an
alarm. An entry is made in the event
memory.
182
Settling 07-12
183
3. Use the keyboard to change the display. Use the
keyboard in the same way as when assigning the zone
names.
4. Confirm your input. On the control unit, enter:
5. The control unit acknowledges your input with a
double "beep" tone and shows Installer Mode.
184 Fire signal transmitter
To change the settings:
1. On the control unit, enter:
2. The LCD display shows: 184:FirePulseOFF
3. Via the keypad, select from the following items and
press:
.
FirePulseOFF
0
Normal 2-tone fire alarm
FirePulseON
Transmits a pulse signal to the outputs
1
connected as „Siren" (81-83=00)
4. Confirm your input. On the control unit, enter:
5. The control unit acknowledges your input with a
double "beep" tone and shows Installer Mode.
185 Key switch auto reset
To change the settings:
1. On the control unit, enter:
2. The LCD display shows: 185:KsAutoRstOFF
3. Via the keypad, select from the following items and
press:
.
KsAutoRstOFF
The user must manually reset any
0
triggered zones.
KsAutoRstON
The system automatically resets zone types
1
KM or KF when the user activates using
the key switch.
80
.
184
.
185