Device master file (DMF) for BK3120
General remarks
To facilitate communication between control and field bus, the following data
must be entered at the control.
If a device master file for the BK3120 bus coupler can be downloaded, any file in
the Beckhoff download area cannot be used.
Fronius International has made a specially modified DMF file for this bus coupler
available in the DownloadCenter.
Data to be ente-
DP device types
red
Ident_Number
Protocol identification PROFIBUS-DP
Protocol_Ident
DP slave
Stations_Type
FMS/DP device
FMS supp
15 byte user parameter data
User_Prm_Data_Len
Default values for User_Prm_Data (Motorola format)
User_Prm_Data
Default values for User_Prm_Data (Intel format)
User_Prm_Data
Terminal type
Module = "KL6121 structure"
End modules
Offset of analog inputs
Offset of analog outputs
Number of analog inputs
Number of analog outputs
Startbit of analog inputs
Startbit of analog outputs
Number of valid / invalid bits analog inputs
Number of valid / invalid bits analog out-
puts
82
0x0BECE
0
0
1
15
0x00, 0x00, 0x00, 0x00, 0x00,\
0x00, 0x00, 0x80, 0x00, 0x6B,\
0x00, 0x10, 0x00, 0x00, 0x00
0x00, 0x00, 0x00, 0x00, 0x00,\
0x00, 0x00, 0x00, 0x00, 0x63,\
0x00, 0x10, 0x00, 0x00, 0x00
0x33, 0x74
4
4
5
5
0
0
16
16