RxD/TxD-P (3)
DGND (5)
RxD/TxD-N (8)
Profibus pin assignment
For the TS/TPS, MW/TT series:
8
For the TSt series:
8
9
Slave address
Set slave address using the two rotary selector switches.
configuration
Default setting = 11
All addresses are permitted, each address may only appear once on the network.
1
2
3
Important! Ensure that the switches engage properly
4
52
Power source 1
DIN rail
Connect the LocalNet plug on the interconnecting hosepack to the LocalNet
connection on the interface
Connect the LocalNet plug on the interconnecting hosepack to the LocalNet
OUT connection
Connect the LocalNet connection on the power source to the LocalNet IN
connection on the interface using a LocalNet cable
Ensure that all devices and components have been switched off and discon-
nected from the mains
Ensure that the interface has been disconnected from the mains
Move switch to desired position using a screwdriver.
-
Values on the upper switch represent units
-
Values on the lower switch represent tens
0
x 1
0
x 10
Using the original screws, fit the interface lid back into its original position
Power source 2
Shield
DIN rail
Example
Setting address 34:
-
Upper rotary selector switch: 4
-
Lower rotary selector switch: 3
RxD/TxD-P (3)
DGND (5)
RxD/TxD-N (8)