Operating Instructions
RE 4000
WARNING
WARNING
8 010 416/08-10-03
Commissioning
4.1.4
Check LED indication
One or more of the LEDs "1" to "6" (yellow) illuminate when the
related safety doors are opened.
POWER LED (green) illuminates when operating voltage is present.
OUTPUT LED (green) illuminates when the safety outputs 13/14,
23/24 and 33/34 are closed.
ERROR LED (red) flashes if there is an error.
4.1.5
Check external device monitoring (EDM) and reset button
Check external device monitoring (EDM).
Check application with reset function.
No machine movement or operation is to be initiated by resetting
(RESET) the protective device if this can cause a dangerous state
(cf. EN 60204).
In this case an additional measure must be provided, e.g. the
incorporation of the start button in the wiring (cf. Fig. 7).
4.1.6
Check reset function
Stop machine.
Close all protective devices.
Do not press reset button.
Press start button.
The machine must not start before the reset button has been
pressed!
4.2
Error monitoring
The evaluation unit checks the system for errors when the protective
device is opened and closed (from the sensor to the output on the
evaluation unit including monitoring of the relay contacts). If an error
is detected, the evaluation unit is placed in an inhibited state (red
"ERROR" LED flashes; green "OUTPUT" LED off with protective
devices closed and open, green "POWER" LED illuminated). See also
chapter 4.4 "Lifting the inhibit in the case of an error".